Belimo B217+TFRB120 Characterized Control Valve 3/4" 2-Way 4.7Cv Spring Return 100-240V On/Off

Manufacturer

Part Number

B217+TFRB120
Black Friday Price

$371.21

In Stock (6)

delivery box

Usually delivered within 2 days

free shipping

FREE SHIPPING

Authorize Seller Badge
No Hassle Returns

No Hassle Returns

Live-in-stock inventory

Live-in-stock inventory

Fitment guaranteed

Fitment guaranteed

Product Details

The Belimo B217+TFRB120 is a factory-assembled, two-component hydronic control solution combining the B217 Characterized Control Valve (CCV) with the TFRB120 spring return actuator. Designed for precise on/off flow regulation in commercial HVAC hydronic systems, this assembly delivers reliable performance in heating and cooling applications.

Valve Specifications (B217):

  • Valve Type: 2-Way Characterized Control Valve (CCV)
  • Valve Size: 3/4" (DN 20)
  • Flow Coefficient (Cv): 4.7 (9.4 GPM @ Δ 4 psi)
  • Flow Characteristic: Equal percentage
  • Close-off Pressure: 200 psi
  • Body Pressure Rating: 600 psi
  • Leakage Rate: 0% (A–AB)
  • Pipe Connection: Internal thread, NPT (female)
  • Fluid: Chilled or hot water, up to 60% glycol
  • Fluid Temperature Range: 0°F to 250°F (-18°C to 120°C)
  • Ball Material: Stainless steel
  • Stem Material: Stainless steel
  • Stem Seal: EPDM (lubricated)
  • Seat: PTFE
  • Characterized Disc: TEFZEL®
  • Valve Body: Nickel-plated brass
  • Controllable Flow Range: 75°
  • Servicing: Maintenance-free

Actuator Specifications (TFRB120):

  • Actuator Type: Fail-safe, spring return
  • Nominal Voltage: AC 100–240 V, 50/60 Hz
  • Control Signal: On/Off
  • Power Consumption (Running): 2.5 W
  • Power Consumption (Holding): 1.3 W
  • Transformer Sizing: 5 VA
  • Protection Category: IP42 / NEMA 2 (UL Enclosure Type 2)
  • Ambient Temperature Range: -22°F to 122°F (-30°C to 50°C)

Key Features:

  • Equal percentage flow characteristic for precise, stable flow control
  • Characterized disc eliminates control loop hunting and optimizes energy efficiency
  • Spring return actuator ensures fail-safe valve positioning on power loss
  • Comparable Cv values to globe valves of the same pipe size, reducing need for pipe reductions
  • Wide universal input voltage (100–240 VAC) for flexible installation
  • Maintenance-free design for long service life

Typical applications include air handling units (AHUs), heating and cooling coils, fan coil units, unit ventilators, VAV box reheat coils, and hydronic bypass loops. Two-way valves should be installed with the characterized disc positioned upstream per Belimo installation guidelines.

Very easy to order and quick delivery time. Very Happy

Super fast n easy

fast easy experience.

N/A

Great experience, shipped as promised.

Great experience

stated 4 items in stock, now having to wait for the item to become available to ship?

GREAT PRICE AND EASY SHOPPING

Share icon
Return Policy
Returns are easy at Autoplicity

Not happy with a purchase? No problem. We've made returning items as easy as possible. And most purchases can be returned for free for 30 days. Learn more about our Returns Policy